STEROSTAB T Series Three Phase
[KVA : 22 – 800]

 


GENERAL CHARACTERISTICS

COMMON REGULATION OF THE THREE PHASES, PROTECTION DEGREE IP20-IP21

Mains Three-phase
Nominal input voltage 380V or 400V or 415V (**)
Nominal output voltage 380V or 400V or 415V (**)
Output accuracy ±1% RMS
Frequency 50/60 Hz ±5%
Admitted load variation 0 to 100%
Admitted load unbalance up to 100%
Admitted overload 10 times the nominal power during 10 ms, 5 times during 6 s, 2 times for 1 minute
Harmonic distortion <0,2%
Efficiency >99%
Cooling natural air convection
Colour RAL 7035
Protection degree IP21
Installation indoor
Standard fittings voltmeter, pilot lamps

(**) to be specified on the order. Different voltage values available on request.

OPTIONAL FITTINGS
  • SHORT CIRCUIT PROTECTION
  • OVERLOAD PROTECTION
  • OVER/UNDER VOLTAGE PROTECTION
  • SOFT START
  • MANUAL OR AUTOMATIC BY-PASS
  • TROPICALISED CONTROL BOARDS
  • DIGITAL NETWORk ANALYSER DISPLAYING THE ELECTRICAL PARAMETERS
  • ISOLATION TRANSFORMER
  • ADAPTING TRANSFORMER
  • SURGE ARRESTERS
  • IP54 INDOOR OR OUTDOOR VERSION

DOWNLOAD
Product Catalog
Technical Data


STEROSTAB T THREE-PHASE 400V 50/60 HZ

IREM AVRs are designed to deliver the declared power permanently (24/7) under the worst operating conditions, i.e. at full load, at minimum input voltage and max input current and at the declared ambient temperature.


3PH AUTOMATIC VOLTAGE STABILISERS T MODELS

The voltage regulator of T series consists of a three phase variable auto transformer, a three phase series transformer, a low inertia servo driven motor and an electronic control circuit.

The control circuit makes out the average of the voltage values on the three output phases, and makes a constant comparison between this average value and a perfectly steady reference signal. If the difference between the average value and the reference voltage overcomes the limits preset by the AVR precision, a error signal is given out.

This signal, which can be positive or negative depending on the voltage (if it is lower or higher than the nominal one), is amplified and operates the servo driven motor of the variable auto transformer which gives the additive or subtractive voltage necessary to bring the output voltage within the preset stabilisation limits.

The regulation of the output voltage is true RMS, therefore the voltage regulator is unaffected by possible harmonic distortion present on the supplying line. This type of voltage regulator is suitable for well-balanced input lines and a maximum load unbalance among the phases of 50%.